EI 60 fire rating is a 60-minute fire-resistance classification where a construction maintains integrity (E) and insulation (I) for one hour. Integrity prevents flames/smoke passing through; insulation limits the temperature rise on the unexposed face, protecting occupants and nearby materials during the rated time. Compared with EI 30, EI 60 demands tougher glazing, profiles, seals and junctions, and tighter control of installation details.
At a glance
Note: Because the safe-side surface temperature is limited, EI also controls radiant heat to safer levels for people close to the glazing.
EI vs EW vs E - what’s the difference? | |||
|---|---|---|---|
| Property / Class | E (Integrity) | EW (Integrity + Radiation) | EI (Integrity + Insulation) |
| Stops flames/smoke passing | |||
| Limits radiant heat near the element | |||
| Limits temperature rise on unexposed face | |||
| Typical glazing make-up | Integrity fire glass | Radiation-control glass | Insulating fire glass (multi-laminate/intumescent) |
| Typical use cases | Low-proximity zones | When radiation control is enough | Close-proximity, routes, protected spaces, sensitive occupancies |
1) Use a tested, documented assembly
Follow the exact combination of profiles/reinforcements, glazing, beads, seals, intumescent components, fixings and hardware specified in the classification report.
2) Glass type
Specify EI-rated insulating fire glass compatible with the aluminium system. These units are typically multi-laminate/intumescent with defined thickness, edge cover and weight. Do not swap in EW or E glass.
3) Sizes & limits
Respect leaf/pane maximums, aspect ratios, visible edge cover and profile spans/centres from the evidence. Oversizing requires a formal EXAP/assessment.
4) Glazing details
5) Hardware & accessories
Only use listed hinges, locks, closers, panic hardware, drop seals, and any electromagnetic hold-open devices referenced in evidence. Check closer power and clearances for the longer duration.
6) Interfaces & substrates
Install into the tested substrate (e.g., concrete, lined stud). Match perimeter firestopping density/depth and record movement joints and deflection criteria.
7) Identification & maintenance
Apply ID labels, include DoP, installation and O&M manuals, and schedule inspections (glass edges, seals, ironmongery).
EI 60 fire rating is achievable in aluminium systems when the tested build-up is followed precisely.
Scope: Usually fixed lights; openable EI-rated windows are uncommon and must be explicitly tested with their exact operating hardware and seals.
Glazing: Use the tested EI glass (type/thickness) and maintain edge cover and intumescent liners as specified.
Locations: Internal partitions to protected routes; external/boundary applications where insulation is required by strategy. and report.
Spec tips: Confirm pane maximums, permitted mullion/transom types, head/sole details; coordinate ventilation via AOVs or separate systems.
Leaf types: Single/double leaves, with/without overpanels/side-lights – each must be covered by evidence.
Hardware: Only listed hinges, locks, closers, panic devices, drop seals. If hold-open is needed, use an automatic release linked to the fire alarm.
Additional performance: Smoke control (Sa/Sm) is separate to EI; include if required.
Spec tips: Check clearances, closer power, glazing bead type, ironmongery packers, and any kick/guard plates.
Layout: Keep to tested post spacing, deflection limits, and head-of-wall junctions. Unframed/butt-jointed glass is typically not permitted for EI unless specifically tested.
Interfaces: Use only approved firestopping and tested substrates; document any movement joints.
People proximity: EI is preferred where occupants or combustibles may be close to the safe face for extended periods.
Spec tips: For door-integrated screens or full-height runs, ensure the combined assembly is within scope (door + side-light + overpanel).
Build exactly to the documented configuration. If your intended size, hardware, glass or junction isn’t covered, obtain EXAP/assessment before proceeding.
Fire-rated aluminium doorset/screen – EI 60
Provide and install a factory-fabricated aluminium glazed doorset/screen classified to EN 13501-2: EI 60, tested to EN 1634-1/EN 1364-1 as applicable.
Construction, glazing, edge cover, seals, intumescent components, hardware and fixings shall match the tested/classified configuration.
Maximum sizes and aspect ratios shall not exceed those in the classification/assessment.
Install per the manufacturer’s instructions with approved perimeter firestopping.
Provide DoP, classification report, installation and maintenance manuals at handover.
What does EI 60 fire rating mean?
The element maintains integrity and insulation for 60 minutes: no through-flames, and the safe-side temperature rise is limited (ΔTavg ≤ 140 °C; ΔTmax ≤ 180 °C).
When should I choose EI 60 over EI 30 or EW 60?
Choose EI 60 where the strategy requires a full hour of insulation – e.g., higher-risk compartments, protected routes in complex buildings, or close-proximity areas.
Does EI 60 fire rating include smoke control?
No. Smoke control (Sa/Sm) is a separate classification and must be specified and evidenced independently.
Can I mix EI doors with EW screens in one elevation?
Only if the combined assembly (door + screen + overpanel) is covered by evidence. Otherwise keep the elevation to EI or obtain an assessment.
What glass types achieve EI 60 fire rating?
Insulating fire glass (multi-laminate/intumescent) matched to the aluminium system, with specific thickness, weight and edge cover per the report.
Can I oversize panes or change ironmongery?
Not without formal EXAP/assessment. Stick to tested sizes, hardware and construction to retain the EI 60 classification.